At first glance, electrical wiring seems simple. You look up a wire gauge (e.g., 10 AWG) on an ampacity chart, see it handles 30 amps, and select a 30A breaker. But what happens when that wire is run through a 140°F attic? What if four of those wires are bundled inside a conduit? What if the equipment is installed at 10,000 feet of altitude?
Continuous load must not exceed 80% of the derated ampacity (or conversely, the derated ampacity must be ≥ 125% of the continuous load).
Table 310.15(C)(1): 7–9 conductors = 70% 47.85A × 0.70 = 33.5A
Neutrals that carry only unbalanced current (e.g., in a 3-phase wye system) are not counted. Neutrals that carry full load (e.g., single-phase, or non-linear loads with triplen harmonics) are counted.
| Number of Conductors | Percent of Ampacity | |----------------------|---------------------| | 1–3 | 100% | | 4–6 | 80% | | 7–9 | 70% | | 10–20 | 50% | | 21–30 | 45% | | 31–40 | 40% |
Required ampacity = 45A continuous × 1.25 = 56.25A
NEC Table 310.15(B)(2)(a) for 45°C ambient, 90°C insulation = 0.87 55A × 0.87 = 47.85A